23011010

23011010 - Huber Suhner(HUBER+SUHNER)
Увеличить
Краткое описание: 230 V Gas Discharge Tube, 6x8 mm

Дополнительная информация

Gas discharge tube provides 230 V DC sparkover with a ±15% tolerance at 100 V/s. The two-electrode 6 x 8 mm device is supplied without a holder and is specified according to ITU-T K.12. It has less than 1 pF capacitance at 1 MHz, greater than 100 GΩ insulation resistance at 100 V, and a CW power frame rating up to 140 W. The operating temperature range is -40 °C to 85 °C, with storage from -55 °C to 125 °C.
Weight 1.8g
Standard ITU-T K.12
Arc voltage approx. 10 V (@ > 1 A)
Capacitance < 1 pF (@ 1 MHz)
DC sparkover 230 V, +/- 15 % (@ 100 V/s)
Glow voltage approx. 70 V (@ 10 mA)
Product code 9071.99.0547
CW power frame ≤ 140W
DC holdover voltage < 150 ms (@ 135 V)
Product description Gas discharge tube 230 V
Storage temperature -55 ... 125°C
Insulation resistance > 100 GΩ (@ 100 V)
Operation temperature -40 ... 85°C
Alter discharge current ≥ 1 operations (@ 65 Arms, 11 cycles)
Impulse discharge current ≥ 1 operations (@ 30 kA, 8/20 µs)
Ingress protection rating Unmated / IP66, IP68, according to IEC 60529 (24 h of water, 1 m)
Glow-arc transition current < 0.5A
Impulse sparkover 100 V/µs 450V
Impulse sparkover 1000 V/µs 675V

Если у вас не открывается документ, нажмите, чтобы открыть файл в новой вкладке.