2641-100WD-2D-A1

2641-100WD-2D-A1 - Setra System
Увеличить
Краткое описание: Model 264 Low Differential Pressure Transducer
Производитель Setra System

Дополнительная информация

The Setra Model 264 is a low differential pressure transducer designed for HVAC building automation. It uses a dead-ended stainless steel welded capacitive sensing element, requiring minimal amplification and delivering excellent accuracy and long-term stability in critical installations. The product offers a 3-year unconditional warranty and features robust design with brass barbed fittings and an optional conduit cover. It is available in wall and conduit versions for flexible mounting. The Model 264 has been a trusted choice in the HVAC industry for over two decades due to its reliability and quality. Applications include HVAC/R systems, room pressurization for critical environments, energy management systems, variable air volume and fan control (VAV), environmental pollution control, and lab & fume hood control
Range 0 to 0.5in WC
Output 0 to 5VDC
Weight 10Ounces
Mounting 4 screw holes on removable zinc plated steel base (designed for 2.75 inch snap track)
Standard UL 94 V-0
Date Code 3800
Excitation 9 to 30VDC
Span Shift ±0.033 %FS/100°F
Zero Shift ±0.033 %FS/100°F
Adjustments Zero and Span, Accessible on top of case
Circuit Type 3-Wire (Com, Out, Exc)
Overpressure Up to 10PSI
Accuracy (FS) ±1.0%
Case Material Fire-retardant glass filled polyester
Serial Number 1251099
Pressure Media Clean air or similar non-conducting gases
Hysteresis (FS) 0.10%
Output Impedance 100ohms
Max Line Pressure 10PSI
Pressure Fittings 3/16 inch O.D. barbed brass for 1/4 inch push on tubing
Long Term Stability 0.5%FS/YR
Storage Temperature -54 to 121°C
Electrical Connection Screw terminal strip
Operating Temperature -18 to 79°C
Unidirectional ranges 0 to 100in WC
Electrical termination 1/2inches conduit enc.
Non-linearity, BFSL (FS) ±0.96%
Compensated Temperature Range -18 to 65°C
Bidirectional Output at Zero Pressure 2.5VDC
Zero Offset (%FS/G) for 10 inch WC range 0.15
Zero Offset (%FS/G) for 0.1 inch WC range 2.3
Zero Offset (%FS/G) for 0.5 inch WC range 0.5
Zero Offset (%FS/G) for 1.0 inch WC range 0.3
Zero Offset (%FS/G) for 2.5 inch WC range 0.2
Zero Offset (%FS/G) for 0.25 inch WC range 1