2907072
Дополнительная информация
| Bv | 69394/A0 BV |
| Kc | R-R-PCK-2907072 |
| Lr | LR21417906TA |
| Abs | 23-2416092-PDA |
| Csa | CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
| Dnv | Class Guideline DNVGL-CG-0339 (TAA00002K4) |
| Eac | RU-DE.B.00184/20 |
| GTIN | 4055626171289 |
| Rina | ELE382621XG |
| Scip | df2efdd7-dca4-4063-afdd-31a55a8c8c0d |
| Depth | 125mm |
| Shock | 18 ms, 30gin each space direction (according to IEC 60068-2-27) |
| Width | 40mm |
| Height | 130mm |
| EU RoHS | Fulfills requirements, Exemption 7(a), 7(c)-l |
| Cb Scheme | IEC 61010-2-201 |
| Sales Key | CM21 |
| Ul Listed | E123528 |
| China Rohs | EFUP-25 |
| Efficiency | typ. 98% |
| Product Key | CMU143 |
| Ul Approval | UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
| Classnk (nk) | TA22372M |
| Culus Listed | E199827 |
| Hood Version | Stainless steel X6Cr17 |
| Packing Unit | 1pc |
| Eu Reach Svhc | Diboron trioxide (CAS: 1303-86-2); Lead (CAS: 7439-92-1) |
| Input Voltage | 24V DC |
| Max. Capacity | 135Ah |
| Mounting Type | DIN rail mounting |
| No-Load Proof | Yes |
| Inrush Current | ≤ 8A (≤ 4 ms) |
| Product Family | QUINT UPS |
| Switch-on Time | max. 3s |
| Iecee Cb Scheme | DK-68191-M1-UL |
| Battery Position | 4.x |
| Housing Material | Metal |
| Switch-over Time | 0ms |
| Country of Origin | CN |
| Mounting Position | On horizontal DIN rail NS 35/7.5 and NS 35/15 acc. to EN 60715 |
| Number of Outputs | 1 |
| Buffer Time (12 Ah) | 19min |
| Degree of Pollution | 2 |
| Input Voltage Range | 18 ... 30V DC |
| Internal Input Fuse | No |
| LED Signaling Types | DC OK (green), Alarm (red), Bat.-Mode (yellow), SOC (red, green), Data (red, green) |
| Short-Circuit Proof | Yes |
| Degree of Protection | IP20 |
| Ef3.1 Climate Change | 21.01 kg CO2e |
| Side Element Version | Aluminum AlMg3 |
| Customs Tariff Number | 85371091 |
| Electric Strength Max | 35V DC |
| End-of-Charge Voltage | 32V DC |
| Fixed Backup Threshold | 22V DC |
| Minimum Order Quantity | 1pc |
| Signal Stripping Length | 8mm |
| Battery Stripping Length | 8mm |
| UPS Connection in Series | No |
| Battery Connection Method | Screw connection |
| Battery Tightening Torque | 0.5 ... 0.6Nm |
| Voltage Drop Input/Output | 0.4V DC |
| Insulation Characteristics | III(without PE) |
| UPS Connection in Parallel | Yes |
| Weight (excluding packing) | 519.73g |
| Weight (including packing) | 592.3g |
| Reverse Polarity Protection | Yes |
| Charging Time (Max Capacity) | 202.5h |
| Depth (Alternative Mounting) | 42mm |
| Dynamic Activation Threshold | > 1 V / 100ms |
| Signal Conductor AWG (rigid) | 24 ... 16AWG (Cu) |
| Width (Alternative Mounting) | 123mm |
| Battery Conductor AWG (rigid) | 30 ... 10AWG (Cu) |
| Battery Drive Form Screw Head | Slotted L |
| Height (Alternative Mounting) | 130mm |
| Static Boost (Mains Operation) | 25A |
| Voltage Type of Supply Voltage | DC |
| Ambient Temperature (Operation) | -25 ... 70°C (> 60 °C Derating: 2.5%/K) |
| Charging Current (Configurable) | 5A |
| Dynamic Boost (Mains Operation) | 30A (5 s) |
| Output Voltage (Mains Operation) | 24V DC |
| Static Boost (Battery Operation) | 25A |
| Output Voltage (Battery Operation) | 24V DC |
| Switch-on Time (Battery Operation) | 8s |
| MTBF (IEC 61709, SN 29500) @ 25 °C | > 1405000h |
| MTBF (IEC 61709, SN 29500) @ 40 °C | > 910000h |
| MTBF (IEC 61709, SN 29500) @ 60 °C | > 481200h |
| Output Current In (Mains Operation) | 20A |
| Output Current In (Battery Operation) | 20A |
| Depth (Device Depth DIN Rail Mounting) | 125mm |
| Output Voltage Range (Mains Operation) | 18 ... 32V DC |
| Ambient Temperature (Storage/Transport) | -40 ... 85°C |
| Battery Conductor Cross Section (rigid) | 0.2 ... 6mm² |
| Output Voltage Range (Battery Operation) | 19 ... 32V DC |
| Installation Distance Right/Left (Active) | 5 / 5mm (Pout ≥50%) |
| Installation Distance Top/Bottom (Active) | 50 / 50mm (Pout ≥50%) |
| Life Expectancy (Electrolytic Capacitors) | 192072h |
| Selective Fuse Breaking (Mains Operation) | 120A (15 ms) |
| Ambient Temperature (Start-up Type Tested) | -40°C |
| Battery Conductor Cross Section (flexible) | 0.2 ... 4mm² |
| Energy Storage Device Connection in Series | No |
| Installation Distance Right/Left (Passive) | 0 / 0mm (Pout ≥50%) |
| Installation Distance Top/Bottom (Passive) | 40 / 20mm (Pout ≥50%) |
| Selective Fuse Breaking (Battery Operation) | 120A (15 ms) |
| Energy Storage Device Connection in Parallel | Yes, 5 |
| Nominal Capacity (without additional charger) | 3 ... 100Ah |
| End-of-Charge Voltage (Temperature-Compensated) | 25 ... 32V DC |
| Installation Distance Right/Left (Active, Passive) | 0 / 0mm (Pout ≤50%) |
| Installation Distance Top/Bottom (Active, Passive) | 40 / 20mm (Pout ≤50%) |
| Output Power POUT (UN, IOUT = IN) (Mains Operation) | 480W |
| Flammability Rating (UL 94, Housing/Terminal Blocks) | V0 |
| Output Power POUT (UN, IOUT = IN) (Battery Operation) | 480W |
| Output Power POUT (UN, IOUT = Istat.Boost) (Mains Operation) | 600W |
| Output Power POUT (UN, IOUT = Istat.Boost) (Battery Operation) | 600W |
| Battery Conductor Cross Section (flexible, with ferrule with plastic sleeve) | 0.2 ... 4mm² |
| Battery Conductor Cross Section (flexible, with ferrule without plastic sleeve) | 0.2 ... 4mm² |
Если у вас не открывается документ, нажмите, чтобы открыть файл в новой вкладке.