A9N18426

Снят с производства
A9N18426 - Schneider(Schneider Electric)
Увеличить
Краткое описание: C120H - circuit breaker - 3P - 125A - B curve
Производитель Schneider(Schneider Electric)
Статус производства Снят с производства (OBSOLETE)

Дополнительная информация

Miniature circuit breaker provides 3-pole thermal-magnetic protection for AC distribution circuits. It is rated for 125 A at 30 °C and uses a B trip curve with 3 to 5 times In magnetic tripping. Breaking capacity is 15000 A Icn at 400 V AC to EN/IEC 60898-1 and up to 15 kA Icu at 380 to 415 V AC to EN/IEC 60947-2. The DIN-rail mounted device has IP20 protection, toggle control, ON/OFF indication, and a 81 mm by 81 mm by 73 mm body. Operation is specified from -30 °C to 60 °C, with storage from -40 °C to 70 °C.
Depth 73mm
REACH unknown
Range Acti9
Width 81mm
Height 81mm
Standards EN/IEC 60947-2; EN/IEC 60898-1
Curve code B
Network type AC
Product name Acti9 C120
Military Spec False
Rated current 125 at 30 °CA
Product weight 0.615kg
Mounting support 35 mm symmetrical DIN rail
Breaking capacity 15000 A Icn at 400 V AC 50/60 Hz to EN/IEC 60898-1; 10 kA Icu at 440 V AC 50/60 Hz to EN/IEC 60947-2; 15 kA Icu at 380...415 V AC 50/60 Hz to EN/IEC 60947-2; 30 kA Icu at 220...240 V AC 50/60 Hz to EN/IEC 60947-2; 15 kA Icu at <= 375 V DC to EN/IEC 60947-2
Device short name C120H
Network frequency 50/60Hz
Poles description 3P
Device application Distribution
Trip unit technology Thermal-magnetic
IP degree of protection IP20 to IEC 60529
Magnetic tripping limit 3...5 x In
Rated insulation voltage 500 AC 50/60 Hz to EN/IEC 60947-2V
Number of protected poles 3
Product or component type Miniature circuit-breaker
Rated operational voltage <= 375 DC; 380...415 AC 50/60 Hz; 220...240 AC 50/60 Hz; 440 AC 50/60 Hz; 230...400 AC 50/60 HzV
Rated impulse withstand voltage 6 to EN/IEC 60947-2kV
Ambient air temperature for operation -30...60°C