Molded-case circuit breaker provides thermal-magnetic protection for distribution applications in a compact PowerPacT B frame. The breaker is rated 45 A with four protected poles and supports 600Y/347 V AC service with 18 kA interrupting capacity under UL 489. It uses a toggle control, TM-D trip unit, 80% continuous current rating, and terminal-nut electrical connections on both ends. Mechanical endurance is rated for 15000 cycles, and electrical endurance is rated for 10000 cycles at 440 V. The unit is CE marked and certified to UL, IEC, CCC, EAC, CSA, and NOM standards for operation from -25 to 70 °C.
| RoHS |
Yes with Exemption |
| Range |
PowerPact |
| Standards |
NEMA AB1; GB 14048.2; EN/IEC 60947-2; EN/IEC 60947-5-1; CSA C22.2 No 5; NMX J-266; UL 489 |
| Dimensions |
5.4 H x 4.3 W x 3.1 Din |
| Control Type |
Toggle |
| Product Name |
PowerPact B |
| RoHS Version |
2011/65/EU, 2015/863 |
| Mounting Mode |
Clip-on 35 mm symmetrical DIN rail; by screws plate |
| Product Weight |
2.736 (1.241 kg)lb |
| Number of Poles |
4P |
| Breaking Capacity |
65 at 208Y/120 V AC; 65 at 240 V AC; 35 at 480/277 V AC; 35 at 480 V AC; 20 at 250 V DC; 18 at 600Y/347 V ACkA |
| Device Short Name |
BG 045 |
| Network Frequency |
50/60Hz |
| Device Application |
Distribution |
| Line Rated Current |
45A |
| Trip Unit Technology |
Thermal-magnetic TM-D |
| Electrical Connection |
Terminal nut, ON and OFF end |
| Product Certifications |
UL; IEC; CCC; EAC; CSA; NOM |
| Rated Insulation Voltage |
800, IEC 60947-2V |
| Continuous Current Rating |
80% |
| Product or Component Type |
Circuit breaker |
| Rated Operational Voltage |
525, 50/60 Hz, UL 489V AC |
| Ambient Operating Temperature |
-25 to 70°C |
| Rated Impulse Withstand Voltage |
8, IEC 60947-2kV |