FS4000
Дополнительная информация
| En 54-2 | Control and Indicating Equipment compliance |
| En 54-4 | Power Supply Equipment compliance |
| Dimensions | 304 × 222 × 94mm |
| Line wiring | Two-wire |
| Fuse - mains | 4.0A |
| Remote input | 1× input for remote Reset fires / Activate monitored outputs |
| Fuse - battery | 6.0A |
| Mains frequency | 50/60Hz |
| Backup batteries | 2× 12 V lead-acid (gel electrolyte) |
| Storage humidity | ≤80%% RH |
| Fault relay output | 1 (C-NC/NO), potential-freepcs |
| Fire relay outputs | 2 (1× C-NC/NO, 1× C-NO), potential-freepcs |
| Operating humidity | ≤93% (non-condensing) at 40°C% RH |
| Max line resistance | 100Ω |
| Mains supply voltage | 187–252V AC |
| Relay contact rating | 3 A @ 125 VAC, 3 A @ 30 VDCA/V |
| Cpr (eu No. 305/2011) | Declaration of Performance No. 119/12.06.2020; Notified body EVPU 1293 |
| Battery charge voltage | 28V DC |
| Max detectors per line | 32pcs |
| Storage temperature range | 5 to 35°C |
| Current thresholds - Fault | 0–6mA |
| Weight (without batteries) | 0.98kg |
| Operating temperature range | −5 to +40°C |
| Transport temperature range | −10 to +50°C |
| Monitored fire alarm outputs | 2pcs |
| Current thresholds - Duty mode | 6–16mA |
| Recommended battery capacities | 4.5 or 7.0 (C20)Ah |
| Fire detection lines (variants) | 2 / 4 / 6 / 8 |
| Current thresholds - Fire stage 1 | 16–40mA |
| Current thresholds - Fire stage 2 | 40–80mA |
| Current thresholds - Short circuit | >80mA |
| Auxiliary power to external devices | 19–27 / 1.2V DC / A |
| Monitored outputs electrical characteristics | 19–27.5 / 1V DC / A |
Если у вас не открывается документ, нажмите, чтобы открыть файл в новой вкладке.