Краткое описание: circuit breaker Compact 125A 4P 50kA at 380/415V(IEC) EverLink lug
Производитель Schneider(Schneider Electric)
Статус производства Производится (ACTIVE)

Дополнительная информация

Molded-case circuit breaker provides distribution protection with a 4-pole frame and 3 protected poles. The breaker has a 125 A rated current at 40 °C and a 690 V AC 50/60 Hz rated operational voltage. Its TM-D thermal-magnetic trip unit provides LI protection with adjustable long-time pickup from 0.7 to 1 times In and a 1250 A magnetic pickup. The N performance level provides 50 kA breaking capacity at 380 to 415 V AC, and EverLink lug terminals accept flexible copper conductors from 2.5 to 70 mm² or rigid and stranded copper conductors from 2.5 to 95 mm². The device is rated IP40 and IK07, operates from -25 to 70 °C, and has a grey 108 mm by 137 mm by 80 mm body weighing 1.42 kg.
RoHS Yes with Exemption
Depth 80mm
Width 108mm
Height 137mm
Control type Toggle
Product name ComPact NSXm
RoHS Version 2011/65/EU, 2015/863
Rated current 125 at 40 °CA
Product weight 1.42kg
Trip unit name TM-D
Number of poles 4P
Mounting support Plate, DIN rail
Neutral position Left
Trip unit rating 125 at 40 °CA
Device short name NSXm 125N
Network frequency 50/60Hz
Performance level N 50 kA 415 V AC
Device application Protection Distribution
Connection terminals EverLink lug, 2.5...70 flexible copper; 2.5...95 rigid or stranded coppermm²
Trip unit technology Thermal-magnetic
Electrical durability 10000 at 440 V Incycles
Mechanical durability 20000cycles
IP degree of protection IP40 IEC 60529
Rated insulation voltage 800 50/60 HzV AC
Product or component type Circuit breaker
Rated operational voltage 690 50/60 HzV AC
Suitability for isolation Yes, EN/IEC 60947-2
Protected poles description 3D
Trip unit protection functions LI
Rated impulse withstand voltage 8kV
Magnetic protection pick-up range 1250A
Ambient air temperature for storage -50...85°C
Ambient air temperature for operation -25...70°C
Long-time protection pick-up adjustment range 0.7...1x In
Rated service short-circuit breaking capacity 50 at 380...415 V AC 50/60 HzkA
Rated ultimate short-circuit breaking capacity 50 at 380...415 V AC 50/60 HzkA