Molded-case circuit breaker provides distribution protection with a 160 A thermal-magnetic TM-D trip unit. The 4-pole, 4-protected-pole device is rated for AC networks at 50/60 Hz and has a 25 kA Icu breaking capacity at 380/415 V AC. Adjustable long-time pickup covers 0.7 to 1 times the rated current, and the instantaneous pickup is fixed at 1250 A. Fixed backplate mounting uses front screw terminals on a 35 mm connection pitch. The breaker is rated IP40, pollution degree 3, and operates from -25 °C to 70 °C.
| RoHS |
Yes with Exemption |
| Depth |
86mm |
| Range |
EasyPact |
| Width |
140mm |
| Height |
161mm |
| Standards |
IEC 60947-2; EN 60947-2 |
| Network type |
AC |
| Product name |
EasyPact CVS |
| RoHS Version |
2011/65/EU, 2015/863 |
| Mounting mode |
Fixed |
| Rated current |
160 at 40 °CA |
| Product weight |
1.9kg |
| Trip unit name |
TM-D |
| Connection pitch |
35mm |
| Mounting support |
Backplate |
| Range of product |
EasyPact CVS100...250 |
| Device short name |
CVS160B |
| Network frequency |
50/60Hz |
| Poles description |
4P |
| Device application |
Distribution |
| Trip unit technology |
Thermal-magnetic |
| Utilisation category |
Category A |
| Connections terminals |
Screw connection |
| Electrical durability |
12000 at 415 V In, IEC 60947-2cycles |
| Mechanical durability |
25000cycles |
| IP degree of protection |
IP40 |
| Product or component type |
Circuit breaker |
| Protected poles description |
4D |
| Rated impulse withstand voltage |
8, EN/IEC 60947-2kV |
| Long time pickup adjustment range |
0.7...1x In |
| Thermal protection adjustment range |
112...160A |
| Ambient air temperature for operation |
-25...70°C |
| Instantaneous pickup adjustment range |
1250A |
| Service breaking capacity at 380/415 V AC |
25, 50/60 Hz, IEC 60947-2kA |
| Ultimate breaking capacity at 380/415 V AC |
25 Icu, 50/60 Hz, IEC 60947-2kA |