Air circuit breaker is a four-pole EasyPact MVS drawout unit for AC distribution applications. It has an 800 A rated current at 40 °C and a 690 V AC 50/60 Hz rated operational voltage to IEC 60947-2. The N breaking-capacity version provides 50 kA Icu and 50 kA Ics at 220 to 440 V AC. Electronic ETA6G trip-unit protection provides LSIG functions with adjustable long-time, short-time, instantaneous, and ground-fault settings.
| RoHS |
Yes with Exemption |
| Range |
EasyPact |
| Dimensions |
439 height x 556 width x 395 depthmm |
| Network type |
AC |
| Product name |
MVS08N |
| RoHS Version |
2011/65/EU, 2015/863 |
| Mounting mode |
Drawout |
| Rated current |
800 at 40 °CA |
| Product weight |
85kg |
| Trip unit name |
ETA6G |
| Breaking capacity |
50 Icu at 220...440 V AC 50/60 Hz, IEC 60947-2kA |
| Poles description |
4P |
| Device application |
Distribution |
| Trip unit technology |
Electronic |
| Mechanical durability |
20000 with maintenance; 10000 without maintenancecycles |
| Operating temperature |
-5...70°C |
| Breaking capacity code |
N |
| Rated insulation voltage |
1000, 50/60 Hz, IEC 60947-2V AC |
| Product or component type |
Circuit breaker |
| Rated operational voltage |
690, 50/60 Hz, IEC 60947-2V AC |
| Protected poles description |
4P 4d |
| Trip unit protection functions |
LSIG |
| Rated impulse withstand voltage |
12, IEC 60947-2kV |
| Rated service breaking capacity |
50 Ics at 220...440 V AC 50/60 Hz, IEC 60947-2kA |