PCA-BA-20-210-1HC-E11

PCA-BA-20-210-1HC-E11 - Carling Technologies
Увеличить
Краткое описание: AC Residual Current Circuit Breaker with Overcurrent Protection

Дополнительная информация

AC residual-current circuit breaker with overcurrent protection combines equipment leakage interruption with hydraulic-magnetic circuit-breaker tripping. The one-pole 120 VAC configuration uses series-trip overcurrent protection, a handle actuator, 10-32 threaded stud terminals, and front-panel mounting. The breaker provides 30 mA maximum leakage-current trip protection with 25 ms or faster leakage trip time and a 5,000 A maximum interrupting capacity. Integrated red and green LED indicators show line power, leakage fault, overcurrent opening, manual off, and reversed hot-neutral conditions.
RoHS Yes
Phase Single phase
Series PC-Series
Mounting Front panel, 6-32 threaded inserts
Endurance 10000 on-offoperations
Frequency 50/60Hz
Time Delay Instantaneous
Product Type AC residual current circuit breaker with overcurrent protection
RoHS Version 2002/95/EC
Terminal Type 10-32 threaded stud
Current Rating 0.10A
System Voltage 120VAC
Agency Approval UL 1053 Recognized Component and CSA Recognized Component with UL Listed Circuit Breakers
Number of Poles 1
Voltage Ratings 120, 120/240VAC
Dielectric Strength 1480 for 1 minuteVAC
Circuit Configuration Series trip
Insulation Resistance 100 minimum at 500 VDCMΩ
Operating Temperature -35 to +66°C
Leakage Current Trip Time ≤25ms
Leakage Current Trip Level 30 maximummA
Maximum Interrupting Capacity 5000A