Molded-case circuit breaker provides distribution circuit protection with a 250 A line rated current and three-pole construction. The unit is rated for 600 V AC at 50/60 Hz and has an 18 kA interrupting rating at 600 V AC under UL 489. It uses a standard electronic MicroLogic 5.0 LSI trip unit with an 80% continuous current rating. I-Line line connection and load-side lugs support installation with ABC phase connection and Kirk keylock accessory. The breaker is CE marked and certified to UL, CSA, NOM, NEMA, and IEC 60947-2 standards for operation from -25 °C to 70 °C.
| RoHS |
Yes |
| Range |
PowerPact |
| Dimensions |
12.86 H x 8.27 W x 8.05 Din |
| Control Type |
Toggle |
| Product Name |
PowerPact P |
| RoHS Version |
2011/65/EU |
| Product Weight |
32lb |
| Number of Poles |
3P |
| Type of Keylock |
Kirk |
| Breaking Capacity |
AIR 18 kA at 600 V AC 50/60 Hz UL 489; AIR 35 kA at 480 V AC 50/60 Hz UL 489; AIR 65 kA at 240 V AC 50/60 Hz UL 489 |
| Country of Origin |
US |
| Network Frequency |
50/60Hz |
| Device Application |
Distribution |
| Line Rated Current |
250A |
| Terminal Identifier |
AL800M23K |
| Trip Unit Technology |
Electronic, standard, MicroLogic 5.0, LSI |
| Electrical Connection |
I-Line connection line; lugs load |
| Operating Temperature |
-25 to 70°C |
| Breaking Capacity Code |
G |
| Rated Insulation Voltage |
750, IEC 60947-2V |
| Continuous Current Rating |
80% |
| Product or Component Type |
Circuit breaker |
| Rated Operational Voltage |
600, 50/60 Hz, UL 489V AC |
| Rated Impulse Withstand Voltage |
8, IEC 60947-2kV |