Molded case circuit breaker provides overcurrent protection and switching for 240 VAC distribution systems. The 2-pole PowerPacT Q unit is rated for 70 A line current with a 10 kA interrupting rating at 120/208 VAC and 240 VAC. Thermal-magnetic trip technology includes an operating handle, 80 percent continuous current rating, and I-Line line connection with load-side lugs. The breaker is designed for 50/60 Hz AC service, has 8 kV impulse withstand voltage, and is certified to UL, CSA, NOM, and NEMA standards.
| GTIN |
785901629917 |
| RoHS |
Yes |
| Depth |
3.93 in (99.82 mm) |
| Range |
PowerPact |
| Width |
3 in (76.2 mm) |
| Height |
6.47 in (164.34 mm) |
| Standards |
UL; CSA; NEMA; NOM-003-SCFI-2000 |
| Control Type |
Operating handle |
| Product name |
PowerPact Q |
| RoHS Version |
2011/65/EU |
| Mounting mode |
I-Line bracket |
| Number of Poles |
2P |
| Breaking capacity |
10 kA 120/208 V AC 50/60 Hz UL; 10 kA 240 V AC 50/60 Hz UL |
| Network Frequency |
50/60Hz |
| Device Application |
Distribution |
| Line Rated Current |
70A |
| Trip unit technology |
Thermal-magnetic |
| Electrical connection |
I-Line connection, line; Lugs, load |
| Magnetic hold current |
1000A |
| Breaking capacity code |
B |
| Product certifications |
UL; CSA; NOM |
| Continuous current rating |
80% |
| Magnetic tripping current |
1800A |
| Product or Component Type |
Circuit breaker |
| Rated operational voltage |
240 V AC 50/60 Hz UL |
| Rated impulse withstand voltage |
8 ULkV |
| Ambient air temperature for operation |
104…158 °F (40…70 °C) |