DIN-rail AC/DC industrial power supplies provide 80 W, 120 W, 240 W, and 480 W output power options with 12 VDC, 24 VDC, and 48 VDC model variants. The series accepts 85 VAC to 264 VAC input and supports operational DC input from 90 VDC to 350 VDC on applicable models. Convection-cooled operation supports a -40°C to +70°C temperature range with full-load operation up to +60°C. The metal-case supplies provide 150% peak current for up to 4 seconds, adjustable output voltage, power-back immunity, short-circuit protection, overload protection, UL HazLoc Class I Division 2 approval, and ATEX certification.
| Atex |
Certified to EN 60079-0, EN 60079-7, EN 60079-15 |
| RoHS |
Compliant with exemptions 7(a) and 7(c)-I |
| REACH |
REACH SVHC list compliant; REACH Annex XVII compliant |
| Ul Hazloc |
Class I, Division 2, Groups A, B, C, D; T4 |
| Efficiency |
Up to 95% |
| Protection |
Short circuit, overload, overvoltage, over temperature |
| Output Power |
80, 120, 240, 480W |
| Mounting Type |
DIN-rail mount, EN 60715 35x7.5 mm or 35x15 mm |
| Cooling Method |
Natural convection |
| EMC Compliance |
IEC/EN 61000-6-2 and IEC/EN 61000-6-3 |
| Connection Type |
Screw terminal |
| Input Frequency |
45 to 65 operational; 50/60 certifiedHz |
| Load Regulation |
0.5 max from 10% to 90% load% |
| Input Regulation |
0.1 max from minimum to maximum input% |
| Safety Approvals |
IEC/EN/UL 62368-1, IEC/EN/UL 61010-1, UL 508, UL 121201, ATEX EN 60079-0/7/15 |
| Voltage Set Accuracy |
±0.25 max% |
| Operating Temperature |
-40 to +70; full load to +60°C |
| AC Input Voltage Range |
85 to 264 operational; 100 to 240 ratedVAC |
| DC Input Voltage Range |
90 to 350 operational; 100 to 250 certified on applicable modelsVDC |
| Nominal Output Voltage |
12, 24, 48VDC |
| Hold-up Time at 230 VAC |
160 min for 80 W seriesms |
| Peak Current Capability |
150 for up to 4 s% |